板式换热器设计计算与校核计算.pdf
点击次数:33 更新时间:2024-03-08

  题 目: 板式换热器设计及其选用

  目录

  一、说 明 书············································· 2

  二、设计方案· ············································ 3

  三、初步选定· ············································ 4

  (1)已知两流体的工艺参数

  (2 ) 确定两流体的物性数据

  (3 )计算热负荷和两流体的质量流速

  (4 )计算两流体的平均传热温差

  (5 )初选换热器型号

  四、验 证············································· 6

  (1)算两流体的流速 u

  (2 )算雷诺数 Re

  (3 )计算努塞尔特数 Nu

  (4 )求两流体的传热系数 α

  (5 )求污垢热阻 R

  (6 )求总传热系数 K ,并核算

  五、核 算············································· 7

  (1)压强降△ P 核算

  (2 )换热器的换热量核算

  六、结 论············································· 7

  七、设计结果· ············································ 8

  八、附 录············································· 9

  表 1:板式换热器的污垢热阻

  图 1:多程流程组合的对数平均温差修正系数

  九、参考文献· ············································ 9

  1

  一、说 明 书

  2

  现有一块建筑用地,建筑面积为 m ,采用高温水在板式换热器

  中加热暖气循环水。 高温水进入板式换热器的温度为 100℃,出口的温

  度为 75℃;循环水进入板式换热器的温度为 65℃ ,出口的温度为 90 ℃。

  2

  供暖面积热强度为 293 kJ /(m ·h)。要求高温水和循环水经过板式换

  热器的压强降均不大于 100 kPa。请选择一台型号合适的板式换热器。

  (假设板壁热阻和热损失可以忽略)

  已知的工艺参数:

  2

  住宅建筑面积( m )

  2

  供暖面积热强度( kJ /(m ·h)) 293

  流体名称 高温水 循环水

  进口温度(℃) 100 65

  出口温度(℃) 75 90

  压强降( kPa) ≤100 ≤100

  二、设计方案

  (1) 根据热量平衡的关系,求出未知的换热量和质量流量,同时算出

  两流体的平均温度差;

  (2) 参考有关资料、数据,设定总传热系